Part Number Hot Search : 
TVR0518 HAT2143H U15A60PT CPD87R A151K A151K 37324 PSMPT65C
Product Description
Full Text Search
 

To Download S8PE-F96024C Datasheet File

  If you can't view the Datasheet, Please click here to try to view without PDF Reader .  
 
 


  Datasheet File OCR Text:
 Three phase input switch mode Power Supply
S8PE
DIN-rail mounting, 3-phase input Switch mode Power Supply with a range of 5A to 40A output current
* 3 phase 400/480 or 200/230 VAC input * 5, 10, 20 and 40A; 24 VDC output * Higher stability, lower ripple and noise level * Compact and attractive design, easily mounted to DIN rail (for 5, 10 and 20A types) * Natural ventilation, no fan for less maintenance * UL60950 (CSA22.2-60950), UL508 listing (CSA22.2-14) in addition to the CE mark * Conform to EN61000-3-2 * All types can be used for parallel & serial operation
Ordering Information
I S8PE
Input voltage 400/480 VAC 3-phase Power rating 120 W 240 W 480 W 960 W 200/230 VAC 3-phase 120 W 240 W 480 W 960 W Output voltage 24 V 24 V 24 V 24 V 24 V 24 V 24 V 24 V Output current 5A 10 A 20 A 40 A 5A 10 A 20 A 40 A With Front mounting Bracket - - S8PE-F48024C S8PE-F96024C - - - S8PE-J96024C With DIN rail mounting Bracket S8PE-F12024CD S8PE-F24024CD S8PE-F48024CD - S8PE-J12024CD S8PE-J24024CD S8PE-J48024CD -
I Model Number Legend
S8PE 1 2 3 4
1. Input Voltage F: 400-480 VAC 3-phase J: 200-230 VAC 3-phase 2. Power Rating 120: 240: 480: 960: 120 W 240 W 480 W 960 W
3. Output Voltage 24: 24 V 4. Configuration C: Covered type with Front-mounting bracket CD: Covered type with DIN-rail track-mounting bracket
Power Supplies
Three phase input switch mode Power Supply
S8PE
L-99
Specifications
Item Efficiency (typical) Input Nominal Input Voltage Nominal Output Current (Vin = 400 VAC, Pmax) (Vin = 480 VAC, Pmax) (Vin = 230 VAC, Pmax) Voltage range Frequency Current (max.) (Vin = Range min., Pmax) Power factor (typical) (Vin = 400 VAC, Pmax) (Vin = 480 VAC, Pmax) (Vin = 230 VAC, Pmax) Leakage current (max.) (Vin = 400 VAC, Pmax) (Vin = 480 VAC, Pmax) (Vin = 230 VAC, Pmax) Inrush current (max.) (Pmax) (Note 1) Output Voltage adjustment range Tolerance adjustment accuracy Ripple & noise (Pmax.) Load variation influence Input variation influence Temperature variation influence Startup time (max.) Hold time (min.) (Vin = 200 VAC, Pmax) (Vin = 400 VAC, Pmax) (Vin = 480 VAC, Pmax) (Vin = 230 VAC, Pmax) Protection 1.7 s - 21 ms 25 ms - 0.5 A 1.0 A 1.5 A 2.5 A 5A 85% 84% - F: 400...480 VAC 10 A 88% 88% - 20 A 87% 87% - 40 A 90% 90% - 50/60 Hz 1.0 A 2.0 A 3.0 A 5.0 A 5A - - 86% J: 200...230 VAC 10 A - - 88% 20 A - - 89% 40 A - - 91%
340...766 VAC
180..264 VAC
0.58 0.52 - 0.4 mA 0.5 mA - 30 A
0.64 0.59 - 0.9 mA 1.1 mA - 30 A
0.89 0.84 - 1.3 mA 1.6 mA - 40 A
0.89 0.84 - 0.7 mA 0.9 mA - 50 A
- - 0.55 - - 0.3 mA 35 A
- - 0.55 - - 0.4 mA 35 A
- - 0.9 - - 0.7 mA 75 A
- - 0.89 - - 1.4 mA 75 A
22.5..26.4 VDC min. 0.5% 200 mV max. 2% max. 0.5% max. 0.01%/C
1.5 s
- 17 ms 26 ms -
1.0 s - 11 ms 24 ms -
0.1 s
- 14 ms 26 ms -
0.9 s 10 ms - - 20 ms
1.0 s
4 ms - - 10 ms
1.3 s 4 ms - - 8 ms
0.1 s
5 ms - - 13 ms
- Short circuit protection with automatic reset - Over load protection - Over voltage protection (Note 4) Yes (for two units) Yes (for two units) Yes (Green LED) Natural air cooling -10..60 C (de-rating: 2%/C for 50..60 C) -25..85 C 25..85% 500 VAC 50/60 Hz (Output - P .E.) Comply to EN60950 F: 2.5 kVAC 50/60 Hz (Input - P .E.) J: 1.5 kVAC 50/60 Hz (Input - P .E.) 500 M min. at 500 VDC: P - Output .E. EN55022 class A, EN55011 class A, EN50081-2 EN61000-6-2, EN61000-3-2 class A IEC60950, EN60950, UL60950, CSA22.2-60950 UL508 (Listing), CSA22.2-14, EN50178, EN60204-1 10 years (typical) 750 g 1.0 kg 2.65 kg 4.75 kg 750 g 1.0 kg 2.65 kg 4.75 kg
Parallel operation Serial operation Indicator
Others
Heat radiation Ambient temperature (Note 2) Storage temperature Ambient humidity Dielectric strength
Insulation resistance EMC Approved standards Life expectancy (Note 3) Weight
Note 1. Measured at 25 C, and cold start condition. (F: Vin = 480 VAC, J: Vin = 230 VAC, duration < 500 s) 2. For UL and CSA, -105 to 50 C (de-rating: 2%/C for 40-50 C only for 40 A model). 3. Under the ambient temperature of 40 C, and a load rate of 50%. 4. Over voltage protection is provided for 5A, 10A and 20A models. For 40A model, no overvoltage protection is provided.
L-100
Three phase input switch mode Power Supply S8PE
Engineering Data
I Definition of Inrush Current, Start up Time and Hold Time
Input ON AC input voltage Input OFF
Inrush current input application
AC input current
90%
96.5%
Output voltage
Start up time
Hold time
I Overload Protction
The Power supply is provided with an overload protec tion function that protect the load and the power sup ply from possible damage by over current. When the output current rises above between 105 to 130% of the rated current, the protection function is triggered, decreasing the output voltage. When output current falls within the rated range, the overload protection function is automatically cleared.
I Overvoltage Protction
(except for 40 A model)
If output voltage exceed the rated voltage more than 20% (50% at maximum) by some reason, then the output voltage will be turned OFF automatically for safety. To restart the S8PE, turn OFF the input voltage, wait for about one minute, then apply the input power again.
I De-rating Curve
Load (%)
Ambient temperature (C) For UL and CSA the maximum temperature is 50% (with derating of 2%/C from 40 C to 50 C, only for 40 A model) Power Supplies
Three phase input switch mode Power Supply
S8PE
L-101
Operation
I Block Diagram
S8PE-F12024CD/J12024CD (5 A) S8PE-F24024CD/J24024CD (10 A)
Input Line Fuses
P .E. Supply Voltage Control And Adjustment Module
RFI filter
Control Module
S8PE-F48024C (20 A) S8PE-F48024CD/J48024CD (20 A)
Input Line Fuses
P .E.
RFI filter
Driving
Opto-isolator
Control Module
S8PE-F96024C/J96024C (40 A)
Input Line Fuses
P .E. Driving
RFI filter
Opto-isolator
Output Voltage Control Module
Control Module
L-102
Three phase input switch mode Power Supply S8PE
Opto-isolator
Output Voltage Control Module
Dimensions and Installation
Note: All dimensions shown are in millimeters. S8PE-F12024CD/J12024CD (5 A) top view side view bottom view front view
S8PE-F24024CD/J24024CD (10 A) top view side view bottom view front view
x y z { |
AC INPUT L1 AC INPUT L2 AC INPUT L3 Protective Earth (P .E.) DC OUTPUT indicator
} ~
Output Voltage adjustment trimmer V.ADJ DC OUTPUT -V DC OUTPUT +V 35 mm DIN-rail attachment
Three phase input switch mode Power Supply
S8PE
L-103
Power Supplies
S8PE-F48024C (20 A) S8PE-F48024CD/J48024CD (20 A)
top view
side view
front view
side view bottom view
S8PE-F96024C/J96024C (40 A) side view front view
top view
bottom view
x y z { |
AC INPUT L1 AC INPUT L2 AC INPUT L3 Protective Earth (P .E.) DC OUTPUT indicator
} ~
Output Voltage adjustment trimmer V.ADJ DC OUTPUT -V DC OUTPUT +V 35 mm DIN-rail attachment for S8PEF48024CD/J48024CD type only Fixing bracket for S8PE-F48024C type only
L-104
Three phase input switch mode Power Supply S8PE
Notice
Three phase input operation when one phase is missing
The S8PE will in most cases continue to operate even after the loss of one phase of the supply. The perfor mance specifications are of course not guaranteed under these conditions. As the loss of one phase puts additional stress on some components, the life span of the unit could be shortened. It is prudent therefore to regularly check for signs of the following possible conditions. 1. Input terminals wiring open/loose. 2. Incorrect / no voltage on one or more phases of the supply. 3. Abrupt or periodical loss of input voltage.
Serial Operation
As shown below, the output voltage from each S8PE can be added. Types must be the same.
+V -V Load +V -V
Three phase input switch off
In order to switch off the Power Supply completely: all 3 phases need to be switched off.
Parallel Operation
As shown below, The Power supply can use for paral lel operation. All the output voltage of each S8PEs should be exactly the same. Also, make sure that the thickness and the length of all wires connected to the load are the same to ensure that the wires will have no voltage drop difference. Types must be the same.
Mounting
To improve and maintain the reliability of the Power Supply over a long period, adequate consideration must be taken to heat radiation. The S8PE is designed to radiate heat by natural air cooling, therefore, mount the S8PE so that enough air flow takes place around the power supply. If installing S8PEs closely, keep the minimum dis tance of 10 cm at 50 C ambient, 5 cm at 20 C am bient.
Generating () Output Voltage
An output of can be generated as shown below, since the S8PE has a floating output.
-V
+V -V Load
+V -V
+V -V
Load
Load
+V
Three phase input switch mode Power Supply
S8PE
L-105
Power Supplies
Safety Precautions
I Safety Signal words
This document uses the following signal words to mark safety precautions for the S8PE. These precautions pro vide important information for the safe application of the product. You must be sure to follow the instructions pro vided with safety signal words. Indicates information that, if ignored, could possibly result in loss of life or seriously injury.
!WARNING
!Caution
Indicates information that, if ignored, could result in relatively serious or minor injury, damage to the product, or faulty operation.
!WARNING
Be sure to connect the grounding line Not doing so may result in electric shock.
!Caution
Do not touch the S8PE while the power is being supplied or immediately after the power is turned OFF. Otherwise hot Switching Power Supply.
!Caution
Do not attempt to disassemble the Power Supply or touch its internal parts while power is being supplied. Doing so may result in electric shock.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527. Cat. No. M044-E1-04 In the interest of product improvement, specifications are subject to change without notice.
L-106
Three phase input switch mode Power Supply S8PE


▲Up To Search▲   

 
Price & Availability of S8PE-F96024C

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X